Selection of a conductor stringing block is a chain of six decisions. Each one narrows the next, and the expensive mistakes are almost always made at the first and the fourth: the conductor envelope is described loosely, and the groove is chosen from a picture instead of from the fitting that has to pass through it. This guide walks the chain in order, with the values that can be checked and the questions that should be answered before a purchase order is issued.
The six decisions at a glance
- Define the conductor and fitting envelope.
- Fix the sheave diameter.
- Fix the rated load and the number of wheels.
- Choose the sheave material and the groove.
- Choose the structure, connection and surface protection.
- Plan the verification and the document set.
Decision 1: Define the conductor and fitting envelope
Start with the outer diameter, not the nominal section. A 630 mm² ACSR conductor is roughly 33 to 34 mm across depending on stranding and steel core; a 400 mm² conductor is smaller. The sheave groove has to fit the actual diameter, and the groove width has to pass the compression tube, which is larger than the conductor itself.
Record four values before opening any catalogue:
- Conductor outer diameter, from the drum label or the manufacturer's data sheet.
- Maximum outer diameter of the compression tube or repair joint that must pass the block.
- Maximum stringing tension from the tension calculation, per conductor.
- Whether OPGW or ADSS is strung in the same operation, and its diameter.
If any of these is missing, the selection is a guess. A block that fits the conductor but not the joint will stop the pull at the first joint, and the fix at site is usually a replacement block delivered on an expedited freight, not a file and a hammer.
Decision 2: Fix the sheave diameter
The sheave diameter controls the bend radius of the conductor under tension and the effort needed to pull it. The series below is the practical mapping used in Chinese transmission work and is a sound baseline for export projects.
| Sheave OD | Conductor section | Typical application |
|---|---|---|
| Φ508 mm | LGJ-400 and below; ordinary optical cable | 110–220 kV lines, distribution work, light and easy to handle |
| Φ660 mm | LGJ-500 to LGJ-630 | 220–500 kV, the mainstream size for medium and large sections |
| Φ822–Φ830 mm | LGJ-630 to LGJ-800 | 500 kV, transitional large-diameter size |
| Φ916 mm | LGJ-720 to LGJ-1000 | 500–800 kV, common for large-section conductors |
| Φ1040 mm | LGJ-1000 to LGJ-1250+ | 1000 kV UHV projects, where bend stress must be kept very low |
Above the table sit two requirements. For 500 kV and above, use a sheave of at least Φ800 mm and check the bend radius against the design documents; for UHV, Φ1040 mm is the normal choice. If the project specification states a minimum bend radius as a multiple of conductor diameter, verify the sheave radius against that number. A larger sheave reduces bend stress and pull force, but it also adds weight and wind area, which matters on a tower installation.
Decision 3: Fix the rated load and the number of wheels
Rated load comes from the tension calculation, with a safety factor of 2.5 to 3 and a 20% to 30% dynamic allowance. Single-wheel blocks typically cover 20 kN to 50 kN. Three-wheel and five-wheel blocks are used for two-, three- and four-bundle conductors, with a combined rating normally between 60 kN and 150 kN.
The wheel count is not only a load question. The wheel spacing has to match the bundle spacing on the tower, otherwise the conductors enter the block at an angle, the load divides unevenly between wheels, and the conductor rubs against the frame instead of sitting in the groove. For a new project, confirm bundle spacing from the tower drawing before ordering a multi-wheel set.
Decision 4: Choose the sheave material and the groove
| Material | Behaviour | Best fit |
|---|---|---|
| MC cast nylon | Light, wear-resistant, self-lubricating, does not score the conductor | Most conductors, OPGW and ADSS; the mainstream choice |
| Aluminium alloy | High strength, long life, harder surface | Very large sections, heavy-duty and repeated use; also used as a frame |
| Rubber-lined | Rubber layer cushions contact and protects the outer surface | Conductors with strict surface requirements, such as aluminium-clad steel |
Two groove dimensions decide whether the block works in practice. The groove bottom radius should be 1.1 to 1.2 times the conductor radius: large enough to seat the conductor without pinching, small enough that the conductor does not roll. The groove width must clear the compression tube; where it does not, specify a large-width block or a dedicated tube-passing block. For OPGW or ADSS, a separate side groove keeps the optical cable out of the main conductor groove and away from the compression pressure.
Decision 5: Choose the structure, connection and surface protection
Single-wheel blocks are for single conductors and ground wires. Three- and five-wheel blocks are for bundled conductors, and the number of wheels should match the bundle count rather than exceed it for an assumed margin. Connection type is a site decision as much as an engineering one: a U-shackle is universal and quick to install; a hook is faster but must have an anti-detachment design; an integrated swivel prevents the conductor from twisting during the pull and is common on higher-value blocks.
Environment drives the finish. In low-temperature regions, specify low-temperature MC nylon to avoid brittle fracture. On coastal or corrosive sites, the frame should be hot-dip galvanised steel or stainless steel, and the bearing seal should be rated for salt and dust. A block that is correct on the drawing but corrodes on the tower is not a cost saving.
Decision 6: Plan the verification and the document set
Before the order is placed, agree what will be measured and what will be filed. At minimum: groove radius and width, wheel runout, rotation resistance, rated load marking, and a static load test at the load stated in the technical annex. The factory report should reference DL/T 1792 test methods and GB/T 23438 product requirements, and the nameplate should carry the model, rating, batch number and date of manufacture.
For bulk orders, add a sampling plan: 3% of the batch, no fewer than three units, with the results recorded against serial numbers. For export to Saudi Arabia, add the PCoC obtained through SABER before shipment and the SCoC for each shipment; a separate SASO certificate is not required for this product category.
A worked example: 220 kV line, LGJ-630/45, two-bundle
The conductor is LGJ-630/45 with an outer diameter of about 33.6 mm, strung as a two-bundle, with a calculated maximum tension of 26 kN per conductor and a compression tube of about 40 mm outside diameter.
- Sheave: Φ660 mm, which is the normal series for LGJ-500 to LGJ-630 and keeps the bend radius within the range used for 220–500 kV work.
- Load: 26 kN × 2.5 = 65 kN, plus a 25% dynamic allowance = about 81 kN. Specify a set rated at 90 kN, for example three wheels at 30 kN each, and confirm the rated load on the nameplate.
- Material: MC nylon, because the conductor is new and surface protection is a project acceptance criterion.
- Groove: bottom radius 1.1–1.2 × 16.8 mm ≈ 18.5–20.2 mm; groove width sized for the 40 mm compression tube rather than for the conductor alone.
- Structure: three-wheel block with wheel spacing matching the bundle spacing, U-shackle connection and an integrated swivel.
- Verification: factory report to DL/T 1792 and GB/T 23438, 3% batch sampling, and a site checklist filed with the batch numbers.
The example is deliberately ordinary. Most projects fail not on exotic conductors but on ordinary ones where the joint was forgotten, the bundle spacing was assumed, or the load was taken from the catalogue rather than from the tension calculation.
Three questions buyers ask
Can one model cover the whole project?
Rarely, and it is usually a false economy. A single model across sections with different conductors means either over-specifying the light sections or under-specifying the heavy ones. A small number of models, matched to the conductor groups on the line, is normally cheaper overall and safer in operation.
Is a larger sheave always better?
No. A larger sheave reduces bend stress and pull force, but it also increases weight, cost and the load on the tower during installation. The right size is the one that satisfies the bend radius requirement for the conductor with a sensible margin, not the largest size in the catalogue.
How much does the finish matter?
More than the catalogue suggests. Galvanising thickness and bearing sealing decide whether the block survives the second project. On coastal sites, a block with a thin coating and a basic seal is a consumable; on inland sites with dry conditions, the same block may last for years.
Conclusion
The six decisions form a sequence for a reason: each one depends on the one before it. Conductor envelope first, then sheave diameter, then load and wheel count, then material and groove, then structure and finish, then verification. A selection that follows the sequence can be explained to an acceptance inspector; a selection that starts from a catalogue page usually cannot.
Ningbo Reach Electric Power Equipments Co., Ltd. manufactures stringing blocks, pullers and tensioners, motorised winches, anti-twist steel wire ropes, cable rollers, hydraulic crimping tools, cable cutters, conductor grips, live-line tools and power safety devices, with more than 20 years of experience in power line construction equipment. The company runs CNC machining, laser cutting, automatic welding, shot blasting and electrostatic spraying lines at Dongcheng Industrial Zone, Dandong Subdistrict, Xiangshan, Ningbo, Zhejiang, China, and provides OEM and ODM support for project-specific blocks. For a selection proposal, contact Lisa Xiang, Director, by WhatsApp or telephone on +86 13968382831.